DV/DT滤波器
型号:AC-DV/DTDV/DTXILIELVBOQISHIYONGYUBAOHUDIANJIDELVBOQI,QIFANGZHIZAIBIANPINQISHUCHUDUAN,NENGYOUXIAODIYANZHANGBIANPINQISHUCHUDUANPWMMAICHONGDESHANGSHENGSHIJIAN,JIANGDIDIANYADEBIANHUALV,DUIBAOHUDIANJIDEJUEYUANYOUJIAOHAODEZUOYONG。BIANPINQIYUDIANJIZHIJIANYUNXINGDIANLANGUOZHANGHUIYINQIDUIDIANJICHANSHENGHUIMIEXINGYINGXIANGFENGZHIDIANYA;DIANLANDEZHANGDUQUJUEYUYONGZAIBIANPINQIZHONGDEDIANLIBANDAOTIDEKAIGUANCISHUHEDIANJIDEDAXIAO,RUGUODIANLANDUANDAO2.5MIZEHUIDAOZHIDIANJICHENGSHOUDEFENGZHIDIANYACHAOGUODIANJIJUEYUANXITONGDEEDINGZHI。RANER,RUGUODIANLANTAIZHANGZEWENTIGENGDA,ZAIZHEIZHONGQINGKUANGXIAJIUXUYAODV/DTLVBOQILAIBAOHUDIANJIBUSHOUFENGZHIDIANYADEHUIMIEXINGYINGXIANG。
产品介绍
成品识别码:
例如:AC-DV/DT-4F0150
(制造商代码:AC为公司简称,DV/DT为产品类别,4为额定电压三相400V,F为绝缘等级,0150为额定电流150A。)
典型电路图:
产品尺寸表:
产品型号 | 额定电流 | 电压等级 | 图号 | 适配变频器功率 | L | W | H | W1 | D |
AC-DV/DT-4F0015 | 15A | 400V | 图A | 5.5KW | 200 | 240 | 200 | 72 | 120 |
AC-DV/DT-4F0020 | 20A | 400V | 图A | 7.5KW | 200 | 240 | 200 | 72 | 120 |
AC-DV/DT-4F0030 | 30A | 400V | 图A | 11KW | 200 | 240 | 200 | 92 | 120 |
AC-DV/DT-4F0040 | 40A | 400V | 图A | 15KW | 200 | 240 | 200 | 92 | 120 |
AC-DV/DT-4F0050 | 50A | 400V | 图A | 18.5KW | 245 | 250 | 200 | 96 | 182 |
AC-DV/DT-4F0060 | 60A | 400V | 图A | 22KW | 245 | 250 | 200 | 96 | 182 |
AC-DV/DT-4F0080 | 80A | 400V | 图A | 30KW | 245 | 250 | 200 | 96 | 182 |
AC-DV/DT-4F0090 | 90A | 400V | 图A | 37KW | 245 | 250 | 200 | 96 | 182 |
AC-DV/DT-4F0120 | 120A | 400V | 图A | 45KW | 245 | 250 | 200 | 108 | 182 |
AC-DV/DT-4F0150 | 150A | 400V | 图A | 55KW | 245 | 250 | 200 | 120 | 182 |
AC-DV/DT-4F0200 | 200A | 400V | 图B | 75KW | 330 | 310 | 420 | 220 | 270 |
AC-DV/DT-4F0250 | 250A | 400V | 图B | 90KW | 330 | 310 | 430 | 220 | 270 |
AC-DV/DT-4F0260 | 260A | 400V | 图B | 110KW | 380 | 330 | 430 | 250 | 335 |
AC-DV/DT-4F0290 | 290A | 400V | 图B | 132KW | 380 | 340 | 430 | 250 | 335 |
AC-DV/DT-4F0330 | 330A | 400V | 图B | 160KW | 380 | 340 | 430 | 250 | 335 |
AC-DV/DT-4F0390 | 390A | 400V | 图B | 185KW | 380 | 350 | 430 | 250 | 335 |
AC-DV/DT-4F0490 | 490A | 400V | 图B | 250KW | 350 | 390 | 430 | 250 | 280 |
AC-DV/DT-4F0600 | 600A | 400V | 图B | 280KW | 350 | 370 | 430 | 250 | 280 |
AC-DV/DT-4F0840 | 840A | 400V | 图B | 315KW | 385 | 400 | 500 | 250 | 320 |
AC-DV/DT-4F1000 | 1000A | 400V | 图B | 450KW | 460 | 400 | 500 | 250 | 395 |
AC-DV/DT-4F1400 | 1400A | 400V | 图B | 560KW | 500 | 400 | 540 | 265 | 420 |
AC-DV/DT-6F0080 | 80A | 690V | 图B | 75KW | 330 | 290 | 410 | 200 | 280 |
AC-DV/DT-6F0120 | 120A | 690V | 图B | 110KW | 380 | 340 | 400 | 250 | 330 |
AC-DV/DT-6F0150 | 150A | 690V | 图B | 132KW | 340 | 390 | 420 | 250 | 265 |
AC-DV/DT-6F0215 | 215A | 690V | 图B | 160KW-200KW | 340 | 390 | 450 | 250 | 265 |
AC-DV/DT-6F0250 | 250A | 690V | 图B | 220KW | 350 | 390 | 460 | 250 | 280 |
AC-DV/DT-6F0330 | 330A | 690V | 图B | 250KW-300KW | 350 | 400 | 500 | 250 | 280 |
AC-DV/DT-6F0390 | 390A | 690V | 图B | 315KW-380KW | 370 | 400 | 480 | 250 | 300 |
AC-DV/DT-6F0410 | 410A | 690V | 图B | 400KW | 420 | 445 | 520 | 320 | 350 |
AC-DV/DT-6F0575 | 575A | 690V | 图B | 450KW | 460 | 445 | 520 | 320 | 390 |
AC-DV/DT-6F0600 | 600A | 690V | 图B | 560KW | 460 | 445 | 550 | 320 | 390 |
AC-DV/DT-6F0810 | 810A | 690V | 图B | 710KW-800KW | 810 | 485 | 560 | 320 | 430 |
PWM逆变器直接驱动电机时会产生较高dv/dt的共模电压,并由此产生轴承电流和共模漏电流以及严重的电磁干扰(EMI)。特别是当逆变器通过长线电缆与电机连接时,由于电缆中分布参数的影响,会在电机端产生电压反射现象,从而在电机端会产生2倍以上的过电压,导致线圈绝缘失败。dv/dt滤波器可以降低电机电缆传输线效应电压的增大而降低衰减率,并减少在电机端子上所发生的峰值电压。
产品应用:
1、dv/dt滤波器是设计用于保护电机的滤波器,由于变频器与电机之间运行电缆过长会引起对电机产生毁灭性影响峰值电压。电缆的长度取决于用在变频器中的电力半导体的开关次数和电机的大小,如果电缆短到2.5米则会导致电机承受的峰值电压超过电机绝缘系统的额定值。然而,如果电缆太长则问题更大,在这种情况下就需要用dV/dT滤波器来保护电机不受峰值电压的毁灭性影响。
2、用于绝缘系统电压强度未知或不够的电动机。
3、dv/dt滤波器限制电压上升率(500V/S)。
4、滤除载波脉冲方波上的寄生杂波。
5、电机与变频器线长距离>200m时建议加装dv/dt滤波器(长度超过300米时请加装正弦波滤波器或使用屏蔽电缆)。
6、电抗器的任意两相电抗值之差不大于+3%。
7、绝缘耐温等级:F级(155℃)以上,H级(180℃)以上。
8、加上滤波器之后dv/dt<800V/us,电机端的线电压峰值小于1.5倍的直流电压。
技术规格:
工作电压:400VAC、690VAC(40℃)
额定电流:5~1400A(40℃)
工作频率:50/60Hz
开关频率:2~8KHz
防护等级:IP00-IP20
绝缘等级:Class F、H
温度范围:-25℃ to +85℃(40℃以上需要降级)
电缆长度:<1000m
额定电压降:8~12%
电压谐波失真:~5%
过载:2倍电流30S 1.5倍电流1分钟
温 升:≤70K,噪音:≤65dB。
抗电强度:铁芯-绕组 3000VAC/50Hz/5mA/10s无飞弧击穿(工厂测试)
绝缘电阻:1000VDC绝缘阻值≥100MΩ
执行标准:
IEC289:1987电抗器
GB10229-88电抗器(eqvIEC289:1987)
JB9644-1999半导体电气传动用电抗器。
使用环境:
1、海拔高度不超过2000米;
2、运行环境温度-25度至+45度,相对湿度不超过90%;
3、安装在户内,防止剧烈震动,周围无有害气体或者粉尘的场合,无易燃易爆物品;
4、周围环境应有良好的通风条件,如装在柜内,应加装通风设备。
5、电抗器工作时,注意安全距离、严禁触摸,防止高温烫伤或电击。